What versions of the CoDeSys software and the 750-841 firmware are compatible? Or rather what versions can be used without having to set the "alternative Target ID" setting in the fieldbus coupler?
WAGO posts a compatibility chart on its website, informing customers of controller and CoDeSys revision compatibility. Here is the link:
http://www.wago.com/wagoweb/documentation/759/eng_info/t07590333000en.pdf
Regarding the "Alternative Target ID" setting in the 750-841's Web Based Management, this feature is used to resolve variations between legacy CoDeSys and 750-841 firmware revisions.
This feature needs to be enabled under the following circumstances:
CoDeSys project uses PLC target firmware 11 or earlier, and Firmware in 750-841 is revision 12 or greater
CoDeSys project uses PLC target firmware 12 or greater, and Firmware in 750-841 is revision 11 or earlier
This feature needs to be disabled under the following circumstances:
CoDeSys project uses PLC target firmware 11 or earlier, and Firmware in 750-841 is revision 11 or earlier
CoDeSys project uses PLC target firmware 12 or greater, and Firmware in 750-841 is revision 12 or greater